modbus_read_registers - read many registers
int modbus_read_registers(modbus_t *ctx, int addr, int nb, uint16_t *dest);
The modbus_read_registers() function shall read the content of the nb
holding registers to the address addr
of the remote device. The result of
reading is stored in dest
array as word values (16 bits).
You must take care to allocate enough memory to store the results in dest
(at least nb * sizeof(uint16_t)
).
The function uses the Modbus function code 0x03 (read holding registers).
The function shall return the number of read registers if successful. Otherwise it shall return -1 and set errno.
modbus_t *ctx;
uint16_t tab_reg[64];
int rc;
int i;
ctx = modbus_new_tcp("127.0.0.1", 1502);
if (modbus_connect(ctx) == -1) {
fprintf(stderr, "Connection failed: %s\n", modbus_strerror(errno));
modbus_free(ctx);
return -1;
}
rc = modbus_read_registers(ctx, 0, 10, tab_reg);
if (rc == -1) {
fprintf(stderr, "%s\n", modbus_strerror(errno));
return -1;
}
for (i=0; i < rc; i++) {
printf("reg[%d]=%d (0x%X)\n", i, tab_reg[i], tab_reg[i]);
}
modbus_close(ctx);
modbus_free(ctx);